Specifications |
fifty-five point three two |
fifty-five point three three |
fifty-five point three four |
| Contact specifications |
| Contact configuration |
2 CO (DPDT) |
3 CO (3PDT) |
4 CO (4PDT) |
| Rated current / maximum peak current a |
10/20 |
10/20 |
7/15 |
| Rated voltage / maximum switching voltage V AC |
250/400 |
250/400 |
250/400 |
| Rated load AC1 VA |
two thousand and five hundred |
two thousand and five hundred |
one thousand seven hundred and fifty |
| Rated load ac15 (230 V AC) VA |
five hundred |
five hundred |
three hundred and fifty |
| Single phase motor rating (230 V AC) kw |
zero point three seven |
zero point three seven |
zero point one two five |
| Breaking capacity dc1:30/110/220 V A |
10/0.25/0.12 |
10/0.25/0.12 |
7/0.25/0.12 |
| Minimum switching load MW (v/ma) |
300 (5/5) |
300 (5/5) |
300 (5/5) |
| Standard contact material |
AgNi |
AgNi |
AgNi |
| Coil specification |
| Nominal voltage (UN) |
V AC(50/60 Hz) |
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 |
| V DC |
6 - 12 - 24 - 48 - 60 - 110 -125 - 220 |
| Rated power ac/dc VA (50 Hz) /w |
1.5/1 |
1.5/1 |
1.5/1 |
| Operating range |
AC |
(0.8…1.1)UN |
(0.8…1.1)UN |
(0.8…1.1)UN |
| DC |
(0.8…1.1)UN |
(0.8…1.1)UN |
(0.8…1.1)UN |
| Holding voltage ac/dc |
0.8 UN / 0.5 UN |
0.8 UN / 0.5 UN |
0.8 UN / 0.5 UN |
| Required voltage ac/dc |
0.2 UN / 0.1 UN |
0.2 UN / 0.1 UN |
0.2 UN / 0.1 UN |